EPA Section 608 test topics: Core, Type I, Type II and Type III
The short version: to work on stationary refrigeration and air-conditioning equipment you need EPA Section 608 certification. Everyone sits the Core; then Type I covers small appliances, Type II high-pressure equipment and Type III low-pressure equipment, and passing all four is Universal. EPA publishes the topics each part covers. This page is that list, for all four.
Read from EPA's Section 608 test topics on October 20, 2026. Each list below is EPA's, in EPA's words.
How the test works
The format is set by the regulation itself, 40 CFR Part 82, Subpart F, Appendix D (Standards for Becoming a Certifying Program for Technicians). In its words:
All Type I, Type II and Type III, certification tests will include 25 questions from Group I and 25 questions from Group II. Universal certification tests will include 25 questions from Group I and 75 questions from Group II (with 25 from each of the three sector-specific areas). Group I will ask questions in the following areas: 1. Environmental impact of CFCs, HCFCs, and substitute refrigerants 2. Laws and regulations 3. Changing industry outlook Group II will ask questions covering sector-specific (i.e., Type I, Type II, Type III) issues in the following areas: 4. Leak detection 5. Recovery Techniques 6. Safety 7. Shipping 8. Disposal
The passing score for the closed-book Type I, Type II, Type III and Universal certification test is 70 percent. The passing score for Type I certification tests using the mail-in format is 84 percent.
The certification test for Type I (if taken as part of a Universal certification), Type II, Type III, and Universal technicians is a closed-book exam.
In the topic lists, Group I is the Core and Group II is the part for your equipment type. EPA's lists are older than parts of the current rule: a topic like “R-22 phaseout date” is still on them, and our questions test what the regulation says today.
Core
AEnvironmental Impacts7 topics
- 1.Destruction of ozone by chlorine
- 2.Presence of chlorine in chlorofluorocarbon (CFC) and hydrochlorofluorocarbon (HCFC) refrigerants
- 3.Identification of CFC, HCFC, and hydrofluorocarbon (HFC) refrigerants (not chemical formulas, but idea that R-12 is a CFC, R-22 is an HCFC, R-134 is an HFC, etc.)
- 4.Idea that CFCs have higher ozone-depletion potential (ODP) than HCFCs, which in turn have higher ODP than HFCs
- 5.Understanding of the atmospheric effects from the types of refrigerants
- 6.Health and environmental effects of stratospheric ozone depletion
- 7.Evidence of stratospheric ozone depletion and role of CFCs and HCFCs
BClean Air Act and Montreal Protocol7 topics
- 1.CFC phaseout date
- 2.R-22 phaseout date
- 3.Venting prohibition at servicing
- 4.Venting prohibition at disposal
- 5.Venting prohibition on substitute refrigerants
- 6.Maximum penalty under the Clean Air Act
- 7.Montreal Protocol (the international agreement to phase out production of ozone-depleting substances)
CSection 608 Regulations7 topics
- 1.Definition/identification of high and low-pressure refrigerants
- 2.Definition of system-dependent versus self-contained recovery/recycling equipment
- 3.Identification of equipment covered by the rule (all air-conditioning and refrigeration equipment containing CFCs or HCFCs except motor vehicle air conditioners)
- 4.Need for third-party certification of recycling and recovery equipment
- 5.Standard for reclaimed refrigerant [Air Conditioning, Heating, and Refrigeration Institute (AHRI) Standard 700-2016]
- 6.The sales restriction
- 7.The Clean Air Act prohibition on venting
DSubstitute Refrigerants and oils3 topics
- 1.Absence of "drop-in" replacements
- 2.Incompatibility of substitute refrigerants with many lubricants used with CFC and HCFC refrigerants and incompatibility of CFC and HCFC refrigerants with many new lubricants (includes identification of lubricants for given refrigerants, such as esters with R-134; alkylbenzenes for HCFCs)
- 3.Fractionation problem--tendency of different components of blends to leak at different rates
ERefrigeration3 topics
- 1.Refrigerant states (vapor versus liquid) and pressures at different points of refrigeration cycle; how/when cooling occurs
- 2.Refrigeration gauges (color codes, ranges of different types, proper use)
- 3.Leak Detection
FThree R Definitions3 topics
- 1.Recover
- 2.Recycle
- 3.Reclaim
GRecovery Techniques2 topics
- 1.Need to avoid mixing refrigerants
- 2.Factors affecting speed of recovery (ambient temperature, size of recycling or recovery equipment, hose length and diameter, etc.)
HDehydration Evacuation1 topic
- 1.Need to evacuate system to eliminate air and moisture at the end of service
ISafety6 topics
- 1.Risks of exposure to refrigerant (e.g., oxygen deprivation, cardiac effects, frost bite, long-term hazards)
- 2.Personal protective equipment [gloves, goggles, self-contained breathing apparatus (SCBA)-in extreme cases, etc.]
- 3.Reusable (or "recovery") cylinders versus disposable cylinders [ensure former Department of Transportation (DOT) approved, know former's yellow and gray color code, never refill latter]
- 4.Risks of filling cylinders more than 80 percent full
- 5.Use of nitrogen rather than oxygen or compressed air for leak detection
- 6.Use of pressure regulator and relief valve with nitrogen
JShipping1 topic
- 1.Labels required for refrigerant cylinders (refrigerant identification, DOT classification tag)
206 practice questions for Core, each citing the regulation it rests on · EPA's page
Type I · Small appliances
ARecovery Requirements3 topics
- 1.Definition of "small appliance"
- 2.Evacuation requirements for small appliances with and without working compressors using recovery equipment manufactured before November 15, 1993
- 3.Evacuation requirements for small appliances with and without working compressors using recovery equipment manufactured after November 15, 1993
BRecovery Techniques6 topics
- 1.Use of pressure and temperature to identify refrigerants and detect noncondensables
- 2.Methods to recover refrigerant from small appliances with inoperative compressors using a system-dependent or "passive" recovery device (e.g., heat and sharply strike the compressor, use a vacuum pump with non-pressurized recovery container)
- 3.Need to install both high and low side access valves when recovering refrigerant from small appliances with inoperative compressors
- 4.Need to operate operative compressors when recovering refrigerant with a system-dependent ("passive") recovery device
- 5.Should remove solderless access fittings at conclusion of service
- 6.Hydrofluorocarbon (HFC)-134a (also called R-134a) as likely substitute for chlorofluorocarbon (CFC)-12 (also called R-12)
CSafety1 topic
- 1.Decomposition products of refrigerants at high temperatures
111 practice questions for Type I, each citing the regulation it rests on · EPA's page
Type II · High-pressure appliances
ALeak Detection3 topics
- 1.Signs of leakage in high-pressure systems (excessive superheat, traces of oil for hermetics)
- 2.Need to leak test before charging or recharging equipment
- 3.Order of preference for leak test gases [nitrogen alone best, but nitrogen with trace quantity of hydrochlorofluorocarbon (HCFC)-22 (also called R-22) better than pure refrigerant]
BLeak repair requirements4 topics
- 1.Allowable leak rate for commercial and industrial process refrigeration
- 2.Allowable leak rate for other appliances containing more than 50 pounds of refrigerant
- 3.Leak repair recordkeeping
- 4.Extensions to the timeframe to repair leaks that exceed the threshold leak rate
CRecovery Techniques4 topics
- 1.Recovering liquid at beginning of recovery process speeds up process
- 2.Other methods for speeding recovery (chilling recovery vessel, heating appliance or vessel from which refrigerant is being recovered)
- 3.Methods for reducing cross-contamination and emissions when recovery or recycling machine is used with a new refrigerant
- 4.Need to wait a few minutes after reaching required recovery vacuum to see if system pressure rises (indicating that there is still liquid refrigerant in the system or in the oil)
DRecovery Requirements7 topics
1.Evacuation requirements for high-pressure appliances in each of the following situations
- a.Disposal
- b.Major versus non-major repairs
- c.Leaky versus non-leaky appliances
- d.Appliance (or component) containing less versus more than 200 pounds
- e.Recovery/recycling equipment built before versus after November 15, 1993
- 2.Definition of "major" repairs
- 3.Prohibition on using system-dependent recovery equipment on systems containing more than 15 pounds of refrigerant
ERefrigeration4 topics
- 1.How to identify refrigerant in appliances
- 2.Pressure-temperature relationships of common high-pressure refrigerants [may use standard temperature-pressure chart--be aware of need to add 14.7 to translate pounds per square inch gauge (psig) to pounds per square inch absolute (psia)]
- 3.Components of high-pressure appliances (receiver, evaporator, accumulator, etc.) and state of refrigerant (vapor versus liquid) in them
- 4.The idea that hydrocarbons are not approved for retrofits
FSafety2 topics
- 1.Shouldn't energize hermetic compressors under vacuum
- 2.Equipment room requirements under American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) Standard 15 (oxygen deprivation sensor with all refrigerants)
175 practice questions for Type II, each citing the regulation it rests on · EPA's page
Type III · Low-pressure appliances
ALeak Detection6 topics
1.Order of preference of leak test pressurization methods for low-pressure systems
- a.Hot water method or built-in system heating/pressurization device such Prevac
- b.Nitrogen
- 2.Signs of leakage into a low-pressure system (e.g., excessive purging)
- 3.Maximum leak test pressure for low-pressure centrifugal chillers
- 4.Leak inspection requirements for appliances that exceed the leak rate
- 5.Reporting for chronically leaking appliances
BLeak repair requirements2 topics
- 1.Allowable annual leak rate for commercial and industrial process refrigeration
- 2.Allowable annual leak rate for other appliances containing more than 50 pounds of refrigerant
CRecovery Techniques5 topics
- 1.Recovering liquid at beginning of recovery process speeds up process
- 2.Need to recover vapor in addition to liquid
- 3.Need to heat oil to 130°F before removing it to minimize refrigerant release
- 4.Need to circulate or remove water from chiller during refrigerant evacuation to prevent freezing
- 5.High-pressure cut-out level of recovery devices used with low-pressure appliances
DRecharging Techniques2 topics
- 1.Need to introduce vapor before liquid to prevent freezing of water in the tubes
- 2.Need to charge centrifugals through evaporator charging valve
ERecovery Requirements8 topics
1.Evacuation requirements for low-pressure appliances in each of the following situations
- a.Disposal
- b.Major versus non-major repairs
- c.Leaky versus non-leaky appliances
- d.Appliance (or component) containing less versus more than 200 pounds
- e.Recovery/recycling equipment built before versus after November 15, 1993
- 2.Definitions of "major" and "non-major" repairs
- 3.Allowable methods for pressurizing a low-pressure system for a non-major repair (controlled hot water and system heating/pressurization device such as Prevac)
- 4.Need to wait a few minutes after reaching required recovery vacuum to see if system pressure rises (indicating that there is still liquid refrigerant in the system or in the oil)
FRefrigeration2 topics
- 1.Purpose of purge unit in low-pressure systems
- 2.Pressure-temperature relationships of low-pressure refrigerants
GSafety2 topics
- 1.Equipment room requirements under ASHRAE Standard 15 (oxygen deprivation sensor with all refrigerants)
- 2.Under ASHRAE Standard 15, need to have equipment room refrigerant sensor for R-123
173 practice questions for Type III, each citing the regulation it rests on · EPA's page